Example: Increasing load, asymmetric P load sharing
A
G
B
G
1
100
20
60
0
40
80
90
130
110
150
Power
[%]
Load
[kW]
Time
s1
3
4
2
Parameters
s1 = Asymmetric P load sharing Set point
Points on graph
1. Genset A and Genset B share the load equally. Asymmetric P load
sharing would required Genset B to run below the minimum.
2. The load rises.
3. The load on Genset B will be more than the minimum if Genset A uses
asymmetric P load sharing. The power management system therefore
increases the load on Genset A until it reaches its asymmetric P load
sharing set point.
4. The load continues to increase. The power management system keeps
Genset A at its asymmetric P load sharing set point, and varies the load
on Genset B.
DESIGNER'S HANDBOOK 4189340911K UK Page 252 of 521