Why Deif SGC 120 Controller sends a Crank-start command immediately after power on?
- RRachael BellSep 2, 2025
If the Deif Controller sends a Crank-start command immediately after power on, ensure that the controller's output terminal is not directly connected to the starter relay. The controller's output should be given to an intermediate relay which should in-turn power the starter relay. The controller can get permanently damaged and will need to be replaced if this precaution is not taken. Check start-relay connection with the suitable controller terminal. Verify the configuration for Start mode and the Start relay output polarity in the Controller's Configuration mode.