EasyManua.ls Logo

Dell PowerEdge R630 - Page 125

Dell PowerEdge R630
197 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 71. Removing the safety ground wire
1. #6-32 nut 2. spring washer
3. grounding post 4. safety ground wire
Assembling the DC input power wires
NOTE: For equipment using (4860) V DC power supply units (PSUs), a qualified electrician must perform all connections
to DC power and to safety grounds. Do not attempt connecting to DC power or installing grounds yourself. All electrical
wiring must comply with applicable local or national codes and practices. Damage due to servicing that is not authorized by
Dell is not covered by your warranty. Read and follow all safety instructions that came with the product.
1. Strip the insulation from the ends of the DC power wires, exposing approximately 13 mm (0.5 inch) of copper wire.
NOTE: Reversing polarity when connecting DC power wires can permanently damage the power supply or the system.
2. Insert the copper ends into the mating connectors and tighten the captive screws at the top of the mating connector by
using a Phillips #2 screwdriver.
NOTE:
To protect the power supply from electrostatic discharge, the captive screws must be covered with the rubber
cap before inserting the mating connector into the power supply.
3. Rotate the rubber cap clockwise to fix it over the captive screws.
4. Insert the mating connector into the PSU.
Figure 72. Assembling the DC Input Power Wires
1.
DC wire RTN 2. DC power connector
Installing and removing system components 125

Table of Contents

Other manuals for Dell PowerEdge R630

Related product manuals