AH500 Programming Manual
2-30
SM Function
CPU5X0-RS2
CPU5X0-EN
CPU5X1-RS2
CPU5X1-EN
CPU560-EN2
OFF
ON
STOP
RUN
RUN
STOP
Attribute
Default
*SM1181
When trigger 7 is triggered and the email is
being sent; SM1181 is ON.
×
×
OFF
R OFF
*SM1182
When trigger 7 is triggered and there is an
SMTP server response timeout, SM1182 is ON.
×
×
OFF
R OFF
*SM1183
When trigger 7 is triggered and there is an
SMTP server response error, SM1183 is ON.
×
×
OFF
R OFF
*SM1184
When trigger 7 is triggered and the size of the
attachment exceeds the limit, SM1184 is ON.
×
×
OFF
R OFF
*SM1185
When trigger 7 is triggered and the attachment
is not found, SM1185 is ON.
×
×
OFF
R OFF
*SM1186
It is the switch of trigger 8 in the email.
×
×
OFF
R
OFF
*SM1187
Trigger 8 in the email
×
×
OFF
R
OFF
*SM1188
When trigger 8 is triggered but the email cannot
be sent due to the Ethernet connection failure;
SM1188 is ON.
×
×
OFF
R OFF
*SM1189
When trigger 8 is triggered and the email has
been sent successfully; SM1189 is ON.
×
×
OFF
R OFF
*SM1190
When trigger 8 is triggered but the email cannot
be sent due to email content error; SM1190 is
ON.
×
×
OFF
R OFF
*SM1191
When trigger 8 is triggered and the email is
being sent; SM1191 is ON.
×
×
OFF
R OFF
*SM1192
When trigger 8 is triggered and there is an
SMTP server response timeout, SM1192 is ON.
×
×
OFF
R OFF
*SM1193
When trigger 8 is triggered and there is an
SMTP server response error, SM1193 is ON.
×
×
OFF
R OFF
*SM1194
When trigger 8 is triggered and the size of the
attachment exceeds the limit, SM1194 is ON.
×
×
OFF
R OFF
*SM1195
When trigger 8 is triggered and the attachment
is not found, SM1195 is ON.
×
×
OFF
R OFF
*SM1196
Socket configuration error
×
×
OFF
R/W
OFF
*SM1270
TCP socket 1─The connection is successful.
×
×
OFF
R
OFF
*SM1271
TCP socket 1─The data has been received.
×
×
OFF
R
OFF
*SM1272
TCP socket 1─The data has been sent.
×
×
OFF
R
OFF
*SM1273
TCP socket 1─The connection is being started.
×
×
OFF
R
OFF
*SM1274
TCP socket 1─The connection is being closed.
×
×
ON
R
ON
*SM1275
TCP socket 1─The data is being sent.
×
×
OFF
R
OFF
*SM1276
TCP socket 1─The data is being received.
×
×
OFF
R
OFF
*SM1277
TCP socket 1─Error flag
×
×
OFF
R
OFF
*SM1278
TCP socket 2─The connection is successful.
×
×
OFF
R
OFF
*SM1279
TCP socket 2─The data has been received.
×
×
OFF
R
OFF
*SM1280
TCP socket 2─The data has been sent.
×
×
OFF
R
OFF
*SM1281
TCP socket 2─The connection is being started.
×
×
OFF
R
OFF
*SM1282
TCP socket 2─The connection is being closed.
×
×
ON R ON
*SM1283
TCP socket 2─The data is being sent.
×
×
OFF
R
OFF
*SM1284
TCP socket 2─The data is being received.
×
×
OFF
R OFF
*SM1285
TCP socket 2─Error flag
×
×
OFF
R
OFF
*SM1286
TCP socket 3─The connection is successful.
×
×
OFF
R OFF
*SM1287
TCP socket 3─The data has been received.
×
×
OFF
R OFF
*SM1288
TCP socket3─The data has been sent.
×
×
OFF
R
OFF

Table of Contents