AH500 Programming Manual
6-334
API
Instruction code
Operand
Function
1506 FSINH P
S, D
Hyperbolic sine of the floating-point
number
Device
X Y M S T C HC D L SM SR E PR K 16# $” DF
S
D
Pulse instruction
16-bit instruction (5-6 steps)
32-bit instruction
AH500 AH500 -
Symbol:
S
Source value Double word
D
hyperbolic sine value Double word
Explanation:
1. Hyperbolic sine value=(e
s
-e
-s
)/2.
2. If the absolute value of the conversion result is larger than the value which can be represented
by the maximum floating-point number, the value in D is 16#7F800000, and SM602 is ON.
3. If the absolute value of the conversion result is less than the value which can be represented
by the minimum floating-point number, the value in D is 16#7F800000, and SM601 is ON.
4. If the conversion result is 0, SM600 is ON.
Example:
1. When X0.0 is ON, the hyperbolic sine of the floating-point number in (D1, D0) is stored in (D11,
D10). The hyperbolic sine value in (D11, D10) is the floating-point number.
D1
D0
D11 D10
Single-precision
floating-point number
Hyperbolic sine value
S
D
2. If the absolute value of the conversion result is larger than the value which can be represented
by the maximum floating-point number, SM602 is ON.
3. If the absolute value of the conversion result is less than the value which can be represented
by the minimum floating-point number, SM601 is ON.
4. If the conversion result is 0, SM600 is ON.
Additional result:
If the value in S exceeds the range of values which can be represented by the floating-point
numbers, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2013.