AH500 Programming Manual
7-20
Error code Description
CPU
Status
LED indicator
status
ERROR
BUS
FAULT
16#B315
Invalid segment in connection path
Continue
Keep
Keep
16#E206
The model number for the control mode CPU
and the standby mode CPU are not the same.
Continue Keep Keep
16#E207
The firmware version for the control mode
CPU and the standby mode CPU are not the
same.
Continue Keep Keep
16#E208
Ethernet for the control mode CPU and the
standby mode CPU are not in the same
physical network.
Continue Keep Keep
16#E209
The I/O configurations of the control mode
CPU is not the same as the actual I/O
configurations of the standby mode CPU.
(while checking the validation)
Continue Keep Keep
16#E20A
The I/O configurations of the control mode
CPU is not the same as the actual I/O
configurations of the standby mode CPU.
(after the validation is checked)
Continue Keep Keep
16#E20B
System error
Continue
Keep
Keep
16#E20C
Synchronization error
Continue
Keep
Keep
16#E20D
Validation failed
Continue
Keep
Keep
16#E20E
I/O bus fault
Continue
Keep
Keep
16#E20F
Heart beat error
Continue
Keep
Keep
16#E210
Heart beat communication timeout
Continue
Keep
Keep
16#E211
Synchronization failed
Continue
Keep
Keep
16#E212
The standby mode CPU is being switched.
Continue
Keep
Keep
16#E213
There is no program on the PLC.
Continue
Keep
Keep
16#E214
PLC program is damage.
Continue
Keep
Keep
16#E215
Scan time out
Continue
Keep
Keep
16#E216
CPU access denied
Continue
Keep
Keep
16#E217
System busy (RST)
Continue
Keep
Keep
16#E218
System busy (CLR)
Continue
Keep
Keep
16#E219
Turning on the system
Continue
Keep
Keep
16#E21A
Initialization error
Continue
Keep
Keep
16#E21B
CPU parameters are damage.
Continue
Keep
Keep
16#E21C
Non-latched area error
Continue
Keep
Keep
16#E21D
CPU EIP parameters are damage.
Continue
Keep
Keep
16#E21E
The I/O configuration file does not exist.
Continue
Keep
Keep
16#E21F
The I/O configuration file is damage.
Continue
Keep
Keep
16#E221
PLC program error
Continue
Keep
Keep
16#E230
Ethernet connection error in a redundancy
system
Continue Keep Keep
16#E260
Module on the main backplane slot 0 does not
support a redundancy system.
Continue Keep Keep
16#E261
Module on the main backplane slot 1 does not
support a redundancy system.
Continue Keep Keep
16#E262
Module on the main backplane slot 2 does not
support a redundancy system.
Continue Keep Keep
16#E263
Module on the main backplane slot 3 does not
support a redundancy system.
Continue Keep Keep
16#E264
Module on the main backplane slot 4 does not
support a redundancy system.
Continue Keep Keep
16#E265
Module on the main backplane slot 5 does not
support a redundancy system.
Continue Keep Keep