變流器於開機前會檢查機器會偵測太陽能板到地之間的阻抗,如果這個阻抗值低於
Insulation Settings(隔離設定)裡面的設定值,變流器將會停止運轉,隔離設定
共提供了四種模式:ON(開啟)、Positive Ground(正接地)、Negative Ground
(負接地)和Disable(失能)。安裝人員也可以針對實際狀況設定不同的阻抗。
圖5-14 : 隔離設定
21. Jun 2010 13:50
Grid Settings 5/5
Reconnection Time
[ ]60 s
21. Jun 2010 13:50
Grid Settings 3/5
Fac High Off
Fac High On
Fac High Off T
Fac Low Off
Fac Low On
Fac Low Off T
52.00 Hz
51.95 Hz
2.0 s
48.00 Hz
48.05 Hz
2.0 s
[
[
[
[
[
[
]
]
]
]
]
]
21. Jun 2010 13:50
Grid Settings 2/5
Vac High Off Slow
Vac High On Slow
Vac High Off Slow T
Vac Low Off Slow
Vac Low On Slow
Vac Low Off Slow T
310.0 V
305.0 V
2.0 s
216.0 V
221.0 V
2.0 s
[
[
[
[
[
[
]
]
]
]
]
]
21. Jun 2010 13:50
Grid Settings 1/5
Vac High Off
Vac High On
Vac High Off T
Vac Low Off
Vac Low On
Vac Low Off T
364.0 V
359.0
V
0.0 s
135.0 V
140.0 V
0.1 s
[
[
[
[
[
[
]
]
]
]
]
]
21. Jun 2010 13:50
Grid Settings 4/5
Fac High Off Slow
Fac High On Slow
Fac High Off Slow T
Fac Low Off Slow
Fac Low On Slow
Fac Low Off Slow T
52.00 Hz
51.95 Hz
2.0 s
48.00 Hz
48.05 Hz
2.0 s
[
[
[
[
[
[
]
]
]
]
]
]
Grid Settings頁面包含各種電壓與頻率保護值,這些保護值乃依據各電力法規所
建立,若無特殊需求請勿修改任何保護值。
5.3.7.3.2 Grid Settings
圖5-15 : Grid Settings頁面
Install Settings
21. Jun 2010 13:50
Inverter ID
Insulation
RCMU
Country Germany MV
[ 001 ]
[ --- ]
Grid Settings
[ ]
Reconnection Time
[
]
60 S
Ramp-up Power
20
%/m
Insulation
21. Jun 2010 13:50
Mode
Resistance
ON
200
[
[
]
] kohm
EXIT
ENT