When this Mode is turned on, inverter will maintain reactive power as a constant
value.
5.3.7.4.5 Constant Reactive Power
Figure 5-22 : Constant Reactive Power setting page
Active/Reactive Power
21. Jun 2010 13:50
Constant cosφ
cosφ(P)
Constant Reactive Power
Q(V)
Reactive Power Control
21. Jun 2010 13:50
Mode
Reactive Power (Q/Sn) 0
OFF
[
[
]
]
%
EXIT
ENT
Users can fine-tune the parameters according to their actual need.
5.3.7.4.6 Q(U)
Figure 5-23 : Q(U) setting page
Active/Reactive Power
21. Jun 2010 13:50
Constant cosφ
cosφ(P)
Constant Reactive Power
Q(V)
Reactive Power Control
21. Jun 2010 13:50
Qi limit
Qs limit Ind 44
Cap 44
[
[
]
]
V2i
184.0[ ]
V2s 253.0[ ]
230.0[ ]
V1i
V1s 230.0[ ]
V
V
V
V
Reactive Power Control
21. Jun 2010 13:50
- -[ ]
%
Mode
OFF[ ]
Lock-out Power
- -[ ]Lock-in Power %
Delay Time
10[ ]
s
EXIT
ENT
a
b
c
d
e
f
a
b
c
d
e
f
V2s
V1s
V1i
V2i
V
Q
Q
s limit
Qi limit
60
Turn on PV Inverter