EasyManua.ls Logo

Delta C1000 - Dimension of PE Busbar

Delta C1000
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PE Terminal
Maximum No. of conductor
(DC/AC/Outside)
Screw/Nut size
Torque requirement
(Nm)
4/4/1 M12 45
Figure 4-14 : Dimensions of the PE connection lugs
PE Cable
(Cu)
Minimum total cable size requirement
555 mm
2
PE Cable
(Al)
Minimum total cable size requirement
740 mm
2
4.6.1 Dimension of PE Busbar
60
40
40
(6)M5
(2)Φ13
35
3030
170
20
C1000
Outside DC/AC
55
95
15
20
M12
40
60
41
Installation