UPS Operation
Standby
UPS-1.1
MEASUREMENT
Mode Setting
SETUP
MAINTENANCE EVENT LOGLOG IN
Administrator
MODE SETTING
On-Line Green ECO
Energy
Recycle
Frequency
Conversion
Select to change system mode
10:15
May 25,2018
(Figure 6-30: Select Frequency Conversion Mode)
9
After manually selecting Frequency Conversion mode via the LCD, the UPS will run
in standby mode and the output will be terminated.
10
Press the icon (
UPS-1.1
) located in the upper left corner of the screen to go back to the
Main Screen.
11
Press the ON/ OFF button ( ) once and the following screen will pop up to ask you
if you want to power on the UPS’s inverter. Please select ‘YES’.
Standby
MEASUREMENT
Power Flow
UPS-1.1 SETUP MAINTENANCE EVENT LOG
POWER ON ?
No
Yes
LOG IN
Administrator
10:15
May 25,2018
(Figure 6-31: Power On Reminder Screen)
12
After selection of ‘YES’ to start up the UPS’s inverter, each power module will start up
and perform self-inspection.
After the self-inspection is completed, the UPS will automatically transfer to run in
frequency conversion mode and the output frequency will be the same as setup value.
Now, the tri-color LED indicator illuminates green and the following screen appears. For
the tri-color LED indicator location, please refer to Figure 2-11.