7-30
Modulon DPH Series
Bypass
1
2
3
4
5
6
UPS-1.1
SETUP MAINTENANCE EVENT LOGLOG IN
Administrator
MEASUREMENT
Dry Contact Setting
DRY CONTACT SETTING
INPUT
OUTPUT
Event Type
Normally Open
Normally Open
Normally Open
Normally Open
Normally Open
Normally Open
None
None
None
None
None
None
10:15
May 25,2018
Output Dry
Contact No.
Event Selection Type
Output Dry Contact 1
Output Dry Contact 2
Output Dry Contact 3
Output Dry Contact 4
Output Dry Contact 5
Output Dry Contact 6
Select one of the following events as
the setting for each output dry contact.
1. None
2. Load on inverter
3. Load on bypass
4. Load on battery
5. Battery low
6. Battery input abnormal
7. Battery test fail
8. Internal comm. fail
9. External parallel comm. fail (only
applicable to parallel application)
10. Output overload
11. EPO activated
12. Load on manual bypass
13. Battery over temperature
14. Output voltage abnormal
15. Battery need replacement
16. Bypass over temperature
17. Bypass static switch fault
18. UPS over temperature
19. Battery breaker shunt trip
20. Backfeed protection
21. UPS general alarm
Set up NO (normally
open) or NC
(normally closed)
for each output dry
contact.