5-9
5
Installation and Wiring
DPH 200~500kVA
Capacity
200kVA/
200kW
300kVA/
300kW
400kVA/
400kW
500kVA/
450kW
Input
Recommended cable
size (R/ S/ T/ N)
95mm
2
x
2 PCS
150mm
2
x
2 PCS
240mm
2
x
2 PCS
185mm
2
x
3 PCS
Maximum cable size
(R/ S/ T/ N)
300mm
2
x
3 PCS
300mm
2
x
3 PCS
300mm
2
3 PCS
300mm
2
x
3 PCS
Cable lug width 50mm 50mm 50mm 50mm
Screw size M12 M12 M12 M12
Output
Rated current at output
voltage 220V
303A 455A 606A 758A
Recommended cable
size (R/ S/ T/ N)
95mm
2
x
2 PCS
150mm
2
x
2 PCS
240mm
2
x
2 PCS
185mm
2
x
3 PCS
Maximum cable size
(R/ S/ T/ N)
300mm
2
x
3 PCS
300mm
2
x
3 PCS
300mm
2
x
3 PCS
300mm
2
x
3 PCS
Cable lug width 50mm 50mm 50mm 50mm
Screw size M12 M12 M12 M12
Battery
Rated current (12V x 40
PCS batteries)
440A 660A 880A 990A
Recommended cable
size (+/ -/ N)
120mm
2
x
2 PCS
240mm
2
x
2 PCS
185mm
2
x
3 PCS
240mm
2
x
3 PCS
Maximum cable size
(+/ -/ N)
240mm
2
x
4 PCS
240mm
2
x
4 PCS
240mm
2
x
4 PCS
240mm
2
x
4 PCS
Cable lug width 50mm 50mm 50mm 50mm
Screw size M12 M12 M12 M12
Tightening Torque M12=500±20Kgf.cm
UPS’s Bypass Switch (Q0) 1000A
Delta or non-Delta External
Maintenance Bypass Cabinet’s
Input Breaker or Switch (Q1)
400A 600A 800A 1000A
Delta or non-Delta External
Maintenance Bypass Cabinet’s
Bypass Breaker or Switch (Q2)
400A 600A 800A 1000A
Delta or non-Delta External
Maintenance Bypass Cabinet’s
Manual Bypass Breaker or
Switch (Q3)
400A 600A 800A 1000A
Delta or non-Delta External
Maintenance Bypass Cabinet’s
Output Breaker or Switch (Q4)
400A 600A 800A 1000A
External Battery Cabinet’s
Breaker (Q5)
500A 800A 1000A 1200A