OPERATION MANUAL FOR PCS100HV
15
3.4.2. Module state
User can get the ID number, master/slave and PCS100HV Master/slave for single or parallel system.
ADDR (HEX)
Definition
Description
RW
OA
Scale
Unit
Min
Max
Default
11E4
EN_PR_STATE_DAM
Operations state of PCS Module
0: Initial
1: Standby
2: DC Preload
3: AC Preload
4: AFE Start
5: Black Start
6: Sync Start
7: SA Normal
8: GC Normal
9: SA2GC
10: GC2SA
11: Fault
12: Test Mode (only for internal testing purpose)
13: Upgrade
Other: Reserved
R
No
NA
NA
0
16
0
Recommended CMD for inquiring STATE of PCS MODULE (PCS #1 master) is (example):
ID
Function Code
ADDR MSB
ADDR LSB
Length MSB
Length LSB
CRC
01
03
11
E4
00
01
C1 01