OPERATION MANUAL FOR PCS100HV
53
6.6. Reconnection function setting
Table 28 Steps for setting Reconnection function [FIRST RUN / WHEN NEED]
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
1091
0001
1D 27
Auto reconnection function enable
1: Enable auto reconnection
function
[M]
2
01
06
1092
04EC
2F AA
Auto reconnection voltage set high
Unit: 0.1%
Setting value = 110%, means
110%*Vrated
[O]
3
01
06
1093
037B
3D F4
Auto reconnection voltage set low
Unit: 0.1%
Setting value = 89.1%, means
89.1%*Vrated
[O]
4
01
06
1094
1397
80 78
Auto reconnection frequency set high
Unit: 0.01Hz
Setting value = 50.15%, means
50.15%*Frated
[O]
5
01
06
1095
128E
11 E2
Auto reconnection frequency set low
Unit: 0.01Hz
Setting value = 47.50%, means
47.50%*Frated
[O]
6
01
06
1096
003C
6D 37
Auto reconnection time set delay
Unit: s
Setting value = 60, means 60s
[O]
NOTE: Model PCS100HV: Vrated is 230V, Frated=50Hz
Table 29 Steps for disabling Reconnection function
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
1091
0000
DC E7
Auto reconnection function disable
0: Disable auto reconnection
[M]