OPERATION MANUAL FOR PCS100HV
53
6.6. Reconnection function setting
Table 28 Steps for setting Reconnection function [FIRST RUN / WHEN NEED]
Auto reconnection function enable
1: Enable auto reconnection
function
Auto reconnection voltage set high
Unit: 0.1%
Setting value = 110%, means
110%*Vrated
Auto reconnection voltage set low
Unit: 0.1%
Setting value = 89.1%, means
89.1%*Vrated
Auto reconnection frequency set high
Unit: 0.01Hz
Setting value = 50.15%, means
50.15%*Frated
Auto reconnection frequency set low
Unit: 0.01Hz
Setting value = 47.50%, means
47.50%*Frated
Auto reconnection time set delay
Unit: s
Setting value = 60, means 60s
NOTE: Model PCS100HV: Vrated is 230V, Frated=50Hz
Table 29 Steps for disabling Reconnection function
Auto reconnection function disable
0: Disable auto reconnection