OPERATION MANUAL FOR PCS100HV
28
4.1. Installation Configuration
In this part, we mainly pay attention to system configurations linked with installation. For example, how many PCSs are installed, , Basic communication
parameters like IP address, baud rate and etc. Before configuration, please check the system configuration documents.
For these items, a recommended process is as follows,
[M] Step1. Read value stored in PCS;
[O] Step2. Write new value to PCS, if change is necessary;
[O] Step3. Read new value to verify if new setting is applied.
Note:
1. If step2 is processed, step3 is a must operation. If step3 failed, try step2 and step3 again.
2. All these items only could be modified off line, which means they only could be modified in S1 (Standby) and S4 (Fault)