OPERATION MANUAL FOR PCS100HV
58
6.9. Volt-Watt function setting
0
20%
80%
100%
VOLTAGE, V/V
rated
(%)
POWER
, P/S
rated
(%)
-20%
-40%
-100%
90% 95% 100% 115% 120%105% 110%
(V3,P3)
60%
40%
(V4,P4)
-80%
-60%
(V1,P1)
(V2,P2)
Figure 6-3 Volt-Watt control mode limit area
Table 34 Steps for setting Volt-Watt function [FIRST RUN / WHEN NEED]
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
2
01
06
10B7
0001
FC EC
Volt-Watt function enable.
1: Enable.
[M]
3
01
06
10B8-
/
/
Curve points configuration.
The value is different based on
[O]