OPERATION MANUAL FOR PCS100HV
74
Table 50 Clear system fault.
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
0001
0001
19 CA
BMS Stop/Start Command
1: BMS ON
Turn on BMS
[M]
2
01
06
0001
0002
59 CB
BMS Stop/Start Command
2: BMS OFF
Turn off BMS
[M]
NOTE
1. Only need to set the command to the PCS100HV master.
2. The “BMS OFF” command is only available when PCS100HV is “Standby” status.
8.2.2. Clear BMS Fault
EMS need to write “1” to the register[0x0002] of PCS100HV local controller when BMS is failure, then PCS100HV will send reset fault command to the
BMS to clear fault through Modbus TCP.
Table 51 Clear system fault.
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
0002
0001
E9 CA
BMS Fault Clear
1: Fault Clear Command
Clear all faults of BMS
[M]
NOTEOnly need to set the command to the PCS100HV master.