OPERATION MANUAL FOR PCS100HV
29
4.1.1. Communication Configuration [FIRST RUN / WHEN NEED]
Configurations about communication items SHOULD be set before others. Which means that, communication configurations should be done first.
Table 7 Configuration Table for Ethernet Communication.
ADDR
(HEX)
ADDR
(DEC)
TYPE
DEFINITION
DESCRIPTION
Unit
RW
Min
Max
Default
OA
10
16
Uint16
EN_PR_OS_CONFIGURE_IP_ADDR1
IP_ADDR1.XXX.XXX.XXX
NA
RW
0
255
192
No
11
17
Uint16
EN_PR_OS_CONFIGURE_IP_ADDR2
XXX.IP_ADDR2.XXX.XXX
NA
RW
0
255
168
No
12
18
Uint16
EN_PR_OS_CONFIGURE_IP_ADDR3
XXX.XXX.IP_ADDR3.XXX
NA
RW
0
255
1
No
13
19
Uint16
EN_PR_OS_CONFIGURE_IP_ADDR4
XXX.XXX.XXX.IP_ADDR4
NA
RW
0
255
136
No
14
20
Uint16
EN_PR_OS_CONFIGURE_IP_PORT
IP_PORT
NA
RW
0
32767
502
No
The default IP address is 192.168.1.136 and port is 502, if need to set new IP address, please modify the above registers.
Table 8 Set new IP address, for example new IP address=10.7.21.40, port=502
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
10
000A
08 08
Set IP_ADDR1 =10
Set new IP address10.7.21.40
Port:502
[M]
2
01
06
11
0007
98 0D
Set IP_ADDR2 =7
[M]
3
01
06
12
0015
E8 00
Set IP_ADDR3 =21
[M]
4
01
06
13
0028
78 11
Set IP_ADDR4 =40
[M]
5
01
06
13
01F6
48 18
Set IP_PORT =502
[M]
If PCS needs to communicate with BMS of Battery system through Ethernet, user must set the following IP registers. The configuration steps are same
as the above.