OPERATION MANUAL FOR PCS100HV
31
4.1.2. Run Mode / Operation Mode [FIRST RUN / WHEN NEED]
PCS run mode should be set before run. PCS may run in different run modes according to user’s instant requirements.
For example,
at 8:00 PCS could run in grid-tie/grid-following mode under an operation mode as ‘1. Power Set’.
And at 9:00, maybe PCS would be changed to run in Standalone/Grid-forming mode with constant voltage and constant frequency.
Anyway, one run mode should be set first.
The most important key items are listed in “Table 10 Table of Run Mode & Operation Mode”.
For these items, a recommended process is as follows,
[M] Step1. Read value stored in PCS;
[O] Step2. Write new value to PCS, if change is necessary;
[O] Step3. Read new value to verify if new setting is applied.