OPERATION MANUAL FOR PCS100HV
32
Table 10 Table of Run Mode & Operation Mode
ADDR
(HEX)
ADDR
(DEC)
TYPE
DEFINITION
DESCRIPTION
Unit
RW
Min
Max
Default
OA
1000
4096
Uint16
EN_CMD_PCS_RUN_MODE
0: PCS Run with Grid-
Following /Grid-tie mode;
1: PCS Run with Grid-
Forming/Off-grid mode;
Default: 0 - Grid-following
mode
Note: The PCS will be
restored to the default value
every time it is powered on
again.
NA
R/W
0
1
0
No
0610
1552
Uint16
EN_PR_SYS_MASTER_CONFIG
System Master configuration.
0: Master(Default).
1: Slave.
NA
RW
0
1
0
No
1052
4178
Uint16
EN_PR_NUM_OF_PCS_IN_PARA
How many PCS module are
installed in system.
NA
RW
1
5
1
No
1072
4210
Uint16
EN_PR_GC_Q_MODE_SEL
Reactive Power Mode
Selection
0: SPF
1: Power Set (Demand
response)
2: NA
3: Volt-Var
Other: NA
NA
RW
0
3
1
Yes