OPERATION MANUAL FOR PCS100HV
46
6.2. Normal/Soft-Start ramp rates setting
-1 0 1 2 3 4 5 6 7 8
0
20%
40%
60%
80%
100%
TIME, minutes
POWER
, P/S
rated
(%)
Table 18 Steps for setting Normal soft start ramp rates [FIRST RUN / WHEN NEED]
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
1076
0001
AD 10
Enable normal soft start ramp rate
1: Enable with 0.01% Scale
[M]
2
01
06
1077
001C
3C D9
Set normal soft start ramp rate value
Setting normal soft start ramp rate
value = 0.28%
[O]
0.28%Prated/s