OPERATION MANUAL FOR PCS100HV
14
3.4. Get State Info [PERIODIC / WHEN NEED]
Delta do not provide a monitoring application. User can get the operation status and key monitoring information of PCS100HV through Modbus TCP.
3.4.1. System state
System state of PCS could be accessed via address 0x06F4(HEX) of PCS100HV Master for single or parallel system.
ADDR (HEX)
Definition
Description
RW
OA
Scale
Unit
Min
Max
Default
06F4
SYS_STATE_PCS_GLOBAL
Global State of PCS System.
0: Initial
1: Standby
2: GT Power On
3. GT Normal
4. SA Power On
5. SA Soft-start
6. SA Normal
7. Fault
8. Test
9. Upgrade
Other: Reserved
R
No
NA
NA
0
16
0
Recommended CMD for inquiring STATE_PCS_SYSTEM is:
ID
Function Code
ADDR MSB
ADDR LSB
Length MSB
Length LSB
CRC
01
03
06
F4
00
01
C5 70