OPERATION MANUAL FOR PCS100HV
41
5.2. Standalone(SA) mode operation
Power On PCS
To power on the PCS100HV in standalone mode, see the following requirements:
1. After the PCS installation is completed, check to ensure that the upstream breaker to utility gird is in the open state, and the breaker to load is in
the closed state before powering on PCS.
2. And also check to make sure the battery system is powered on and battery system output switch is in closed state.
3. Ethernet communication port (CNS4) of PCS100HV shall be connected to EMS or upper level controller or site controller to establish the
communication link.
Step 1: open the front door.
Step 2: turn the AC and DC switches/disconnects in the front of the cabinet to ON state as shown in Figure 5-1. The PCS powers on and enters standby
mode.
Step 3: set the correct IP address (Default:192.168.1.136) and port number (502) and start communicating with PCS100HV.
Step 4: configure and confirm the right operation mode (Standalone mode) and parameters by following the below table via upper level controller.
Table 16 Parameters in Standalone/Grid-forming Mode
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
c
01
06
1000
0001
4C CA
Set PCS run in SA mode
temporarily.
1: SA/Grid-forming mode.
[M]
01
06
1050
0001
4C DB
Set wiring mode
1: 3P4L
[M]
01
06
1001
0001
1D 0A
PCS ON
Turn to RUN STATE
[M]
01
06
1001
0002
5D 0B
PCS OFF
Turn to STANDBY STATE
[M]
NOTE: The value of register [0x1000] will be restored to the default value every time it is powered on again.