6.11. Voltage average protection function setting
Table 40 Steps for setting voltage average protection function [FIRST RUN / WHEN NEED]
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
10CF
0003
FD 34
Average voltage protection enable
bit 0 = 1: Average under voltage
enable
bit 1 = 1: Average over voltage
enable
[M]
2
01
06
10D0
0462
0F DA
Average voltage OVP voltage value
Setting value = 112.2%, means
112.2%*Vrated
[O]
3
01
06
10D2
012C
2D 7E
Average voltage OVP time value
Setting value = 3, means 3s
[O]
NOTE: Model PCS100HV: Vrated is 230V
Table 41 Steps for disabling voltage average protection function
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
10CF
0000
BD 35
Average voltage protection disable
bit 0 = 0: Average under voltage
disable
bit 1 = 0: Average over voltage
disable
[M]