OPERATION MANUAL FOR PCS100HV
65
6.11. Voltage average protection function setting
Table 40 Steps for setting voltage average protection function [FIRST RUN / WHEN NEED]
Average voltage protection enable
bit 0 = 1: Average under voltage
enable
bit 1 = 1: Average over voltage
enable
Average voltage OVP voltage value
Setting value = 112.2%, means
112.2%*Vrated
Average voltage OVP time value
Setting value = 3, means 3s
NOTE: Model PCS100HV: Vrated is 230V
Table 41 Steps for disabling voltage average protection function
Average voltage protection disable
bit 0 = 0: Average under voltage
disable
bit 1 = 0: Average over voltage
disable