OPERATION MANUAL FOR PCS100HV
49
6.4. High/Low voltage protection function setting
Table 22 Passive anti-islanding voltage limit values
Table 23 Steps for setting high/low voltage protection function [FIRST RUN / WHEN NEED]
Enable high/low voltage protection
bit4 = 1: Over Level 2 enable
bit3 = 1: Over Level 1 enable
bit2 = 1: Under Level 1 enable
bit1 = 1: Under Level 2 enable
bit0 = 0: Under Level 3 disable
Set over/under voltage time scale
bit4 = 0: Over Level 2 scale
0.01s(10ms)
bit3 = 0: Over Level 1 scale
0.01s(10ms)
bit2 = 0: Under Level 1 scale
0.01s(10ms)
bit1 = 0: Under Level 2 scale