EasyManua.ls Logo

Delta PCS100HV - High;Low Voltage Protection Function Setting

Delta PCS100HV
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OPERATION MANUAL FOR PCS100HV
49
6.4. High/Low voltage protection function setting
Table 22 Passive anti-islanding voltage limit values
Table 23 Steps for setting high/low voltage protection function [FIRST RUN / WHEN NEED]
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
107B
001E
7D 1B
Enable high/low voltage protection
bit4 = 1: Over Level 2 enable
bit3 = 1: Over Level 1 enable
bit2 = 1: Under Level 1 enable
bit1 = 1: Under Level 2 enable
bit0 = 0: Under Level 3 disable
[M]
2
01
06
107C
0000
4C D2
Set over/under voltage time scale
bit4 = 0: Over Level 2 scale
0.01s(10ms)
bit3 = 0: Over Level 1 scale
0.01s(10ms)
bit2 = 0: Under Level 1 scale
0.01s(10ms)
bit1 = 0: Under Level 2 scale
[O]

Other manuals for Delta PCS100HV