OPERATION MANUAL FOR PCS100HV
71
7.2. Clear Faults Command [WHEN NEED]
EMS need to send “Clear faults” command to reset the all fault words to “0” in order to clear the unrecoverable faults.
ADDR
(HEX)
ADDR
(DEC)
TYPE
DEFINITION
DESCRIPTION
Unit
RW
Min
Max
Default
OA
1004
4100
Uint16
EN_CMD_CLEAR_ALL_FAULT
Clear all faults of system and
module
0: No action
1: Clear command
NA
R/W
0
1
0
No
Table 49 Clear system fault.
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
1004
0001
0D 0B
1: clear faults command.
Clear all faults of system
and module
[M]
NOTE
1. Only need to set the command to the PCS master, the PCS master will synchronize to the slaves for parallel system.
2. After the fault clearing operation is completed, the value of register will be automatically return to 0.