OPERATION MANUAL FOR PCS100HV
9
3.2. Definitions of States
Table 1 System State Definitions (2-1)
State ID
DC Relay
AC Relay
PWM
Remark
M2
Pre-Load
M1
Pre-Load
Main
S0
Open
Open
Open
Open
Open
Off
PCS initialization stage. PCSs power on, it will initial
hardware /software configuration. Delay 3s to
standby.
S1
Open
Open
Open
Open
Open
Off
System finished initialization. And is waiting for
system configuration or operation commands.
It will check the system fault and warning condition
in standby mode.
S2
Open
Open
Open
Open
Open
Off
System is configured as grid tie mode. The method
of configuration refers to section 3.3-tr16/tr67.And
got PCS on command.
Relays operation follow:
DC Relay M2 Closed ->
DC Pre-Load relay Closed ->
DC Relay M1 Closed ->
DC Pre-Load relay Open ->
AC Pre-Load relay Close ->
AC Main Relay Close ->
AC Pre-Load Relay Open.
Then PCS PWM on.
The relay states are showing at the last line.
Close
Close
Close
Open
Close
Close
Open
On
Close
Open
Close
Open
Close
On