OPERATION MANUAL FOR PCS100HV
43
6. Grid code [FIRST RUN / WHEN NEED]
PCS should be configured before run. Once PCS was configured, core settings are memorized. PCS would load default settings if customer do not want
to change anything.
Core settings are only could be modified when PCS’s state is STANDBY’ or FAULT. If you find that the changes could not be applied, please check
the PCS’s state first.
Note:
(a) We recommend user check settings before run PCS each time, to make sure all the settings are the same as you planed.
(b) Please confirm Main breaker / Contactor for GRID TIE is close.
(c) This chapter applies to the parameter configuration of grid code for different area in grid-connected mode.
(d) To model PCS100HV, only need to select different grid code and enable one or more functions, generally don’t need to modify any detailed curve
point or parameters.