6.7. SPF mode setting
P/S
rated
(%)
100%
100%
-100%
-100%
80%-80%
Q/S
rated
(%)
P_ENTER
60%
-60%
-P_ENTER
Figure 6-1 SPF control mode limit area
Table 30 Steps for setting SPF mode [FIRST RUN / WHEN NEED]
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
109C
0001
8C E4
Enable SPF mode.
1: Enable SPF.
[M]
2
01
06
109D
03E8
1C 5A
Set target PF
PF = 1.000
[M]
3
01
06
109A
005A
2D 1E
Exit level for active power in SPF
Setting value = 9%, means
9%*Prated
[O]
4
01
06
109B
0064
FD 0E
Enter level for active power in SPF
Setting value = 10%, means
[O]