Loading...
OPERATION MANUAL FOR PCS100HV
55
10%*Prated
5
01
06
1097
0258
3C 7C
Set Q maximum
Set reactive power maximum
Default: 60%
[O]
6
01
06
1098
0320
0D CD
Set PF minimum
Set PF minimum
Default: 60%
[O]
7
01
06
1072
0000
2D 11
Set Q mode
0: SPF
[M]
NOTE: Model PCS100HV: Prated is 100kW
Table 31 Steps for disabling SPF mode
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
10DC
0000
4C F0
Disable SPF mode.
0: Disable SPF.
[M]
2
01
06
1072
0001
EC D1
Return to default value
1: Power set (Demand mode)
[M]