OPERATION MANUAL FOR PCS100HV
36
5.1. Grid-tie mode operation
Power On PCS
To power on the PCS100HV in grid-tied mode, see the following requirements:
1. After the PCS installation is completed, check to ensure that the upstream breaker of AC side is in the closed state before powering on PCS.
2. And also check to make sure the battery system is powered on and battery system output switch is in closed state.
3. Ethernet communication port (CNS4) of PCS100HV shall be connected to EMS or upper level controller or site controller to establish the
communication link.
Step 1: open the front door.
Step 2: turn the AC and DC switches/disconnects in the front of the cabinet to ON state as shown in Figure 5-1. The PCS powers on and enters standby
mode.
NOTE:
ON: Vertical, turn counterclockwise to horizontal position to OFF state.
OFF: Horizontal, turn clockwise to vertical position to ON state.