OPERATION MANUAL FOR PCS100HV
37
Figure 5-1 AC and DC disconnects ON location
Step 3: set the correct IP address (Default:192.168.1.136) and port number (502) and start communicating with PCS100HV.
Step 4: configure and confirm the right operation mode (Grid-tied mode) and parameters by following the below table via upper level controller.
Table 13 Parameters of GRID TIE Mode
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
01
06
1000
0000
8D 0A
Set PCS run as GRID TIE mode
0: Grid Tie/Grid-following
[M]
01
06
1050
0000
8D 1B
Set wiring mode
0: 3P3L
[M]
01
06
0610
0000
88 87
Set Master
0: Master
[O]
01
06
1052
0001
ED 1B
Set parallel number
1: single PCS
[O]
01
06
1072
0001
EC D1
Set Power demand mode
1: Power demand mode
[O]
01
06
1073
0000
7CD1
Set Reactive power priority
0: Reactive power priority
[O]