7.3. Heartbeat Signal[PERIODIC]
The EMS needs to send a heartbeat signal to the PCS every 2s. The PCS will continue to detect whether the heartbeat signal has changed within 10s. If
the heartbeat signal remains unchanged, a communication exception fault will be triggered and the PCS will stop running.
ADDR
(HEX)
ADDR
(DEC)
TYPE
DEFINITION
DESCRIPTION
Unit
RW
Min
Max
Default
OA
0000
0000
Uint16
EN_PR_OS_CMD_EMS_PCS_HEARTBEAT
EMS HeartBeat.
EMS HeartBeat 0~255, Updated
every 2s.
(Check with Users)
NA
RW
0
255
0
Yes