EasyManua.ls Logo

Delta PCS100HV - Get Monitoring Info [PERIODIC; WHEN NEED]; System Monitoring

Delta PCS100HV
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OPERATION MANUAL FOR PCS100HV
18
3.5. Get Monitoring Info [PERIODIC / WHEN NEED]
Delta do not provide a monitoring application. User can get the operation status and key monitoring information of PCS100HV through Modbus TCP.
3.5.1. System Monitoring
ADDR
(HEX)
ADDR
(DEC)
TYPE
DEFINITION
DESCRIPTION
Unit
RW
Min
Max
Default
06FF
1791
Uint16
EN_MEAS_SYS_FREQ_GRID
Frequency of Grid
0.01Hz
R
2000
7000
0
0700
1792
Uint16
EN_MEAS_SYS_VOLT_GRID_RS
Vrms of Grid RS
The variable is displayed If Remote
Grid is connected to PCS.(bit1 of
Reg 0x0611 set to “1”).
0.1V
R
0
7000
0
0701
1793
Uint16
EN_MEAS_SYS_VOLT_GRID_ST
Vrms of Grid ST
The variable is displayed If Remote
Grid is connected to PCS.(bit1 of
Reg 0x0611 set to “1”).
0.1V
R
0
7000
0
0702
1794
Uint16
EN_MEAS_SYS_VOLT_GRID_TR
Vrms of Grid TR
The variable is displayed If Remote
Grid is connected to PCS.(bit1 of
Reg 0x0611 set to “1”).
0.1V
R
0
7000
0
0703
1795
Uint16
EN_MEAS_SYS_VOLT_PCS_RS
Vrms of PCS AC RS
0.1V
R
0
7000
0
0704
1796
Uint16
EN_MEAS_SYS_VOLT_PCS_ST
Vrms of PCS AC ST
0.1V
R
0
7000
0
0705
1797
Uint16
EN_MEAS_SYS_VOLT_PCS_TR
Vrms of PCS AC TR
0.1V
R
0
7000
0