8.2.3. Protection Parameters Configuration
If the battery system is included in the system, some protection parameters need to be set before using it. The following table shows the setting steps.
Table 52 Steps for setting demand response mode [FIRST RUN / WHEN NEED]
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC
REF
1
01
06
0618
0C7F
4D A5
BMS Auxiliary Configuration Enable Registers
bitx = 1: Check enable,
bitx = 0: Check disable; x=0-15
b0=1: BMS Communication Check Enable.
b1=1: BMS Fault Check Enable.
b2=1: BMS Warning Check Enable.
b3=1: Battery Voltage High Fault Check Enable.
b4=1: Battery Voltage Low Warning Check
Enable.
b5=1: BMS SOC Fault Check Enable (high/low).
b6=1: BMS SOC Warning Check Enable
(high/low).
b10=1: Battery Cell Volt High Warn Check Enable.
b11=1: Battery Cell Volt Low Warn Check Enable.
Enable all related protection
of Battery system
*Note: Auto recharging function
isn’t enabled.
[M]
2
01
06
0619-
061E
0622-
0623
/
/
Protection threshold setting of SOC, battery DC
voltage, cell voltage.
Refer to the chapter “4.3
Battery Parameter” of
PCS100HV Prototocol.pdf for
more information.
[O]