OPERATION MANUAL FOR PCS100HV
75
8.2.3. Protection Parameters Configuration
If the battery system is included in the system, some protection parameters need to be set before using it. The following table shows the setting steps.
Table 52 Steps for setting demand response mode [FIRST RUN / WHEN NEED]
BMS Auxiliary Configuration Enable Registers
bitx = 1: Check enable,
bitx = 0: Check disable; x=0-15
b0=1: BMS Communication Check Enable.
b1=1: BMS Fault Check Enable.
b2=1: BMS Warning Check Enable.
b3=1: Battery Voltage High Fault Check Enable.
b4=1: Battery Voltage Low Warning Check
Enable.
b5=1: BMS SOC Fault Check Enable (high/low).
b6=1: BMS SOC Warning Check Enable
(high/low).
b10=1: Battery Cell Volt High Warn Check Enable.
b11=1: Battery Cell Volt Low Warn Check Enable.