OPERATION MANUAL FOR PCS100HV
76
Note: The user can enable or disable one or more protection items by setting bitx of register[0x0618] to “1” or “0”.
8.2.4. Auto Recharging Control mode
When the SOC is lower than the set lower limit [0x061F], if the auto-recharging function is enabled through setting the register [0x0618] (bit8=1, bit9=1),
the PCS100HV will automatically start recharging according to the power command set by the register [0x0621].
BMS Auxiliary Configuration Enable Registers
bitx = 1: Check enable,
bitx = 0: Check disable; x=0-15
b8=1: Battery Auto Recharge by SOC Enable.
b9=1: Battery Auto Recharge Power by Set
Enable.
Enable auto-recharging
function of Battery system
*Note: All protection functions
and power limit function are
enabled.
Start charging when SOC is less than 2.5%.
Stop charging when SOC is greater than 10%.
Power command for auto-charging
8.2.5. Manual Recharging Control mode