OPERATION MANUAL FOR PCS100HV
77
bit9=0), the PCS100HV will start recharging according to the power command set by the register [0x1007].
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
0618
0DFF
4D 95
BMS Auxiliary Configuration Enable Registers
bitx = 1: Check enable,
bitx = 0: Check disable; x=0-15
b8=1: Battery Auto Recharge by SOC Enable.
b9=0: Battery Auto Recharge Power by Set
Enable.
Enable manual-recharging
function of Battery system.
*Note: All protection functions
are enabled.
[M]
2
01
06
061F
0019
79 4E
Start charging when SOC is less than 2.5%.
SOC low limit= 2.5%
[O]
3
01
06
0620
0064
89 63
Stop charging when SOC is greater than 10%.
SOC high limit= 10%
[O]
4
01
06
1007
01F4
3C DC
Power command for manual-recharging
Power Command = 50kW
[M]
8.2.6. Power Limit Control function
If the “BMS Power Limitation” function is enabled (bit7=1), then the maximum output power of PCS100HV will be limited by the available charge and
discharge power curve from BMS.
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
0618
0080
08 E5
BMS Auxiliary Configuration Enable Registers
bitx = 1: Check enable,
bitx = 0: Check disable; x=0-15
b7=1: BMS Power Limitation Check Enable.
Enable power limit function.
*Note: All protection functions
and recharging function are
disabled.
[M]