OPERATION MANUAL FOR PCS100HV
44
6.1. Set Grid Code
The register parameters of this chapter will vary depending on the register [0x105B] (Grid code type). When PCS is applied to a certain area, you should
first confirm the applicable grid regulations and set the following register. For Australian regulation AS4777.2-2015, the user need to write the value “6”
to register [0x105B], and 1-5 are used for AS4777.2-2020 and VDE4105 certification, refer to the below table for detail.
No grid code application.
Applicable to Australia Region A grid-connected regulatory certification
Applicable to New Zealand grid-connected regulatory certification
Applicable to German grid-connected regulatory certification
Applicable to Australia Region B grid-connected regulatory certification
Applicable to Australia Region C grid-connected regulatory certification
Default configuration, cannot be applied to specific regions, only for test use.
Table 17 grid code parameter setting (example)
Choose and confirm the
appropriate code according to the
application area.
0: No Set
1: AS4777.2A
2: NZS4777.2
3: VDE4105-2018
4: AS4777.2B