6.1. Set Grid Code
The register parameters of this chapter will vary depending on the register [0x105B] (Grid code type). When PCS is applied to a certain area, you should
first confirm the applicable grid regulations and set the following register. For Australian regulation AS4777.2-2015, the user need to write the value “6
to register [0x105B], and 1-5 are used for AS4777.2-2020 and VDE4105 certification, refer to the below table for detail.
Index
Grid Code Type
Description
0
No Set
No grid code application.
1
AS4777.2A
Applicable to Australia Region A grid-connected regulatory certification
2
NZS4777.2
Applicable to New Zealand grid-connected regulatory certification
3
VDE4105-2018
Applicable to German grid-connected regulatory certification
4
AS4777.2B
Applicable to Australia Region B grid-connected regulatory certification
5
AS4777.2C
Applicable to Australia Region C grid-connected regulatory certification
31
Delta Default
Default configuration, cannot be applied to specific regions, only for test use.
Table 17 grid code parameter setting (example)
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
105B
0006
3D 19
Grid code.
Choose and confirm the
appropriate code according to the
application area.
0: No Set
1: AS4777.2A
2: NZS4777.2
3: VDE4105-2018
4: AS4777.2B
[M]