OPERATION MANUAL FOR PCS100HV
73
8. BMS
8.1. Communication Configuration [FIRST RUN / WHEN NEED]
Please refer to the chapter 4.1.1
8.2. BMS Control, Protection and Recharging
8.2.1. Turn on/off BMS
ADDR
(HEX)
ADDR
(DEC)
TYPE
DEFINITION
DESCRIPTION
Unit
RW
Min
Max
Default
OA
0001
0001
Uint16
EN_PR_OS_CMD_BMS_START
BMS Stop/Start Command
0: NA
1: BMS ON
2: BMS OFF
NA
W
0
2
0
No
0002
0002
Uint16
EN_PR_OS_CMD_BMS_FAULT_CLEAR
BMS Fault Clear
0: NA/No Command
1: Fault Clear Command
NA
W
0
1
0
No
EMS need to write “1” to the register[0x0001] of PCS100HV local controller, then PCS100HV will send BMS ON command to the BMS to TURN ON the
battery system. And write “2” to TURN OFF the battery system.