OPERATION MANUAL FOR PCS100HV
66
6.12. Demand response mode setting
Table 42 Steps for setting demand response mode [FIRST RUN / WHEN NEED]
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
10D4
0001
0C F2
Demand response mode enable
1: Enable demand response mode
[M]
2
01
06
10D5
0000
9C F2
Reactive power demand of DRM3
and DRM7.(AS/NZS4777.2 only)
Setting value = 0, means reactive
power is 0
[O]
NOTE: Model PCS100HV: Vrated is 230V
Table 43 Steps for disabling demand response mode
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
10D4
0000
CD 32
Demand response mode disable
1: disable demand response mode
[M]