OPERATION MANUAL FOR PCS100HV
13
Table 4 Transition Table (3-2)
Any fault is detected.
Delay time depends on
the check time of fault.
Get detail fault info from step2 to step 9.
Detail description about fault definition
please refer to protocol file.
System Alarm: 0x06F8-0x06FE
Module Alarm: 0x11E7-0x11EE
Command Off.
Delay about 1s.
Note: Off command value is 0x02 or 0x00;
If step2 return other value, process step1
first.
Faults cleared.
Delay about 1s.
This transition would be processed
automatically.
Conditions:
Read Register ID: 0x06F8~0x06FE,
Read Register ID: 0x11E7~0x11EE,
All fault bits return 0, except warning bits.
Note: a time delay between command and next state request should be over 50ms.