OPERATION MANUAL FOR PCS100HV
13
Table 4 Transition Table (3-2)
No.
Previous
State(s)
Next
State
Conditions
Register Operation
Remarks
Step(s)
R/W
Register
ADDR
Value
Must
Optio
n
trx4,
tr14
S1,
S2,
S3,
S6,
S7
S4
Any fault is detected.
Delay time depends on
the check time of fault.
1
R
0x06F4
0x07
O
Get detail fault info from step2 to step 9.
Detail description about fault definition
please refer to protocol file.
System Alarm: 0x06F8-0x06FE
Module Alarm: 0x11E7-0x11EE
2
R
0x06F8-
0x06FE
X
O
3
R
0x11E7-
0x11EE
X
O
trx1
S2,
S3,
S6,
S7
S1
Command Off.
Delay about 1s.
1
W
0x1001
0x02/
0x00
M
Note: Off command value is 0x02 or 0x00;
If step2 return other value, process step1
first.
2
R
0x06F4
0x01
O
tr41
S4
S1
Faults cleared.
Delay about 1s.
1
R
0x06F4
0x01
O
This transition would be processed
automatically.
Conditions:
Read Register ID: 0x06F8~0x06FE,
Read Register ID: 0x11E7~0x11EE,
All fault bits return 0, except warning bits.
Note: a time delay between command and next state request should be over 50ms.