OPERATION MANUAL FOR PCS100HV
12
Run Mode: Grid-forming
(Stand Alone)
Command On.
Register map refer to tr12.
Delay about 10s.
Check step1: 0x1000 equal to ‘0x01’-Pass,
If step1 fail, execute step2 until step1 pass.
Check step3: 0x06F4 equal to ‘0x01’-Pass,
If step3 pass, process step4.
Final PCS state is ‘0x05’-SA Soft start mode.
Soft start stage is done.
Delay about 3s.
This transition is being done automatically.
Final PCS state is ‘0x06’-SA Normal run
mode.
Note: a time delay between command and next state request should be over 50ms.
Note2: PCS will respond the corresponding operation only after the system state enters normal operation. for example, the power demand commands
only available under the normal run state of grid-tied mode(0x03), Voltage and Frequency regulation only available under the normal run state of stand-
alone mode.
Note3: The time delay is an approximate time of execution of ONE PCS. It needs an additional about 3 seconds for each PCS for parallel system.