OPERATION MANUAL FOR PCS100HV
57
10B1
Q1->[0x10AB], V1->[0x10AA]
Q2->[0x10AD], V2->[0x10AC]
Q3->[0x10AF], V3->[0x10AE]
Q4->[0x10B1], V4->[0x10B0]
different grid code, please refer to
PCS100HV Protocol.
3
01
06
109A
005A
2D 1E
Exit level for active power in Volt-Var
Setting value = 9%, means
9%*Prated
[O]
4
01
06
109B
0064
FD 0E
Enter level for active power in Volt-
Var
Setting value = 10%, means
10%*Prated
[O]
5
01
06
1072
0003
6D 10
Reactive Power Mode Selection.
3 = Volt-Var
[M]
6
01
06
1001
0001
1D 0A
PCS Power ON
Turn to RUN STATE
[M]
NOTE: Model PCS100HV: Prated is 100kW;
Table 33 Steps for disabling Volt-Var function
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
10A9
0000
5D 2A
Disable Volt-Var function.
0: Disable .
[M]
2
01
06
1072
0001
EC D1
Return to default value
1: Power set (Demand mode)
[M]