EasyManua.ls Logo

Delta PCS100HV - Page 52

Delta PCS100HV
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OPERATION MANUAL FOR PCS100HV
52
bit2 = 0: Over Level 1 scale
0.01s(10ms)
bit1 = 0: Under Level 1 scale
0.01s(10ms)
bit0 = 0: Under Level 2 scale
0.01s(10ms)
3
01
06
1089-
1090
/
/
Protection Value and time
Configuration
The value is different based on
different grid code, please refer to
PCS100HV Protocol.
[O]
Table 27 Steps for disabling high/low frequency protection function
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
1087
0000
3D 23
Disable high/low voltage protection
bit3 = 0: Over Level 2 disable
bit2 = 0: Over Level 1 disable
bit1 = 0: Under Level 1 disable
bit0 = 0: Under Level 2 disable
[M]

Other manuals for Delta PCS100HV

Related product manuals