Loading...
OPERATION MANUAL FOR PCS100HV
61
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
10C0
0003
CD 37
Freq-Watt function enable(Over
frequency).
3: 3-Point Mode (w/ Register 4291.)
[M]
2
01
06
10C6
0003
2D 36
Freq-Watt function enable(under
frequency).
3: 3-Point Mode (w/ Register 4297.)
[M]
3
01
06
10C1-
10C4,
10C7-
10CA,
10CC,
10CE
/
/
Curve points configuration.
The value is different based on
different grid code, please refer to
PCS100HV Protocol.
[O]
Table 37 Steps for disabling Freq-Watt function
STEP
CMD
DESCRIPTION
REMARK
Option
ID(PCS)
Function
Register
Value
CRC REF
1
01
06
10C0
0000
8D 36
Disable Freq-Watt function(Over
frequency).
0: Disable.
[M]
2
01
06
10C6
0000
6D 37
Disable Freq-Watt function(Under
frequency).
0: Disable.
[M]