7.6.4 Battery & Charging Setting
Path: → Battery & Charging Setting
Item Description
Battery Type
Set up the battery type as
VRLA/ LiB (Dry Contact)
*
1
/
LiB
(Integration)
*
2
.
NOTE:
1.
*
1
If you use non-Delta lithium-ion batteries,
please set up the battery type as '
LiB (Dry
Contact)
'. Please refer to
4.1.6 Input Dry
Contacts
and
7.6.6 Dry Contact Setting
. For
more information about configurations of the
lithium-ion batteries, please contact Delta
customer service.
2. *
2
If you use the Delta lithium-ion batteries, please
set up the battery type as '
LiB (Integration)
'. The
item '
LiB (Integration)
' will only appear on the
LCD if you use the Delta lithium-ion batteries with
the optional multifunctional communication card
(MFC) being installed in the SMART slot. Please
contact Delta customer service if you need more
information.
Battery Rating Voltage
Set up the battery voltage rating.
Battery Strings
Set up how many battery strings that are used on site.
Battery Low Warning
Set up the battery low warning voltage.
Battery Cut Off
Voltage
Set up the battery low voltage. In Battery mode, when the
battery low voltage is reached, the battery power will be cut
off, the UPS will shut down, and the connected loads will not
be protected.
Capacity
Set up the battery capacity.
Float Charge Voltage
Set up the float charge voltage.
Equalized Charge
Voltage
Set up the equalized charge voltage.
NOTE:
The item will only show up if the
Battery Type
is set
as '
VRLA
'.