EasyManuals Logo

Delta Ultron Series User Manual

Delta Ultron Series
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #33 background imageLoading...
Page #33 background image
33
4.1.1 Display Port
Before shipment, the display port has been connected to the 10” touch panel with the
designated cable in Delta factory.
4.1.2 REPO Dry Contacts
Connect the REPO dry contacts to a user-supplied switch and you can remotely shut down
the UPS when an emergency occurs. The REPO dry contacts provide normally open (NO)
and normally closed (NC) these two options for use.
(Figure 4-2: REPO Dry Contacts & Schematic)
NOTE:
To enable the normally closed (NC) function, please take out the dry contact card
and remove its Jump CNR3 before you turn on the UPS.
(Figure 4-3: Location of the Dry Contact Card)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Ultron Series and is the answer not in the manual?

Delta Ultron Series Specifications

General IconGeneral
BrandDelta
ModelUltron Series
CategoryUPS
LanguageEnglish

Related product manuals