149
Appendix 1 : Technical Specifications
Model DPS
UPS Capacity
300kVA/
300kW
400kVA/
400kW
500kVA/
500kW
600kVA/
600kW
Input
Nominal Voltage
220/380 Vac, 230/400 Vac, 240/415 Vac
(3Φ4W + G)
Voltage Range 176 ~ 276 Vac*
1
(full load)
Current Harmonic
Distortion
≤ 3%*
2
Power Factor > 0.99
Frequency Range 40 ~ 70 Hz
Output
Voltage
220/380 Vac, 230/400 Vac, 240/415 Vac
(3Φ4W + G)
Voltage Harmonic
Distortion
≤ 1.5% (linear load)
Frequency 50/60 Hz
Overload Capability
≤ 110%: 60 minutes*
3
;
≤ 125%: 10 minutes; ≤ 150%: 1 minute
Display
10” Touch Panel
Interface
Standard
External battery temperature dry contact × 4,
External switch/ breaker status dry contact × 4,
Output dry contact × 6, Input dry contact × 4,
Parallel port × 4, USB type A × 2,
USB type B × 1, RS-232 port × 1,
MODBUS port × 1, BMS (RJ45) × 1,
Ethernet × 1, SMART slot × 1, REPO × 1
Efficiency
Online Mode up to 96.50%
ECO Mode 99%
Battery
Nominal Voltage ± 240 Vdc (Default)
Charge Voltage ± 272 Vdc (adjustable from 204 Vdc to 312 Vdc)