43
ED900 09-2021DL4617-001
dormakaba ED900 Setup and Troubleshooting Instructions Appendix A
Parameter
Value
range
Units
Factory
setting
Description
Factory setting level. Parameter SL is used to determine what data will be reset during factory setting process.
1 - 2
Standard factory settings.
. Mode switch: CLOSE.
• Door closed.
. Press button keypad down button
for greater than s.
• All parameters reset to factory settings.
• Procedure completed when "" on digit displays blinks twice.
• Installed upgrade cards remain valid and do not require reinstallation.
. Learning cycle required.
Extended factory settings.
. Mode switch: CLOSE.
• Door closed.
. Set SL=
. Press button keypad down button for greater than s.
• All parameters reset to factory settings.
• Installed upgrade cards deleted from operator memory
• Procedure completed when "" on digit displays blinks twice.
• Parameter SL automatically reset to .
. Control unit and upgrade cards can be used independently (delivery status).
. Learning cycle required..
Opening angle.
. Door opening angle set during learning cycle is displayed.
. Opening angle can only be changed during learning cycle.
. Due to installation and parameter tolerances, display value may not match actual door
position.
- °
Automatic / manual door closer mode
-
. Automatic mode. This mode is applicable whenever door is mainly opened
automatically and where motion detectors are installed.
. Mode is optimized for high frequency use.
. Full energy upgrade card provides for higher door opening and closing speeds.
. In case door is blocked during a closing cycle, operator reverses automatically.
. Driving phase is optimized to provide reliable closing cycles.
. Keep closed force (wind load control) parameter FH and Push & Go function
parameter PG are only available in automatic mode.
. Manual mode. This mode is applicable whenever door is mainly used manually
and only rarely automatically.
. In case door is blocked during a closing cycle, door will stop at its current position.
. Driving phase optimized for manual opening cycles.
. Power assist function parameter hf is only available in manual mode.
Power assist activation angle
. Setting of door activation angle for Power assist function (hF).
. Higher settings of hA result in better spring force compensation for easier manual
opening.
. Power assist function is more sensitive the smaller the activation angle.
- °
A.. Driving parameters detail.