EasyManua.ls Logo

Dräger P3U - Electrical Connections; 2 Wire Connection

Dräger P3U
140 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
Electrical connections
Electrical connections
The electrical wiring may be laid and connected only by a qualified electrician,
who must also comply with the appropriate regulations – a screened or un-
screened cable (such as LiY, LiYCY) may be used.
2-wire connection
Connection to central device with at least 2-wire cable, 0.5 (AWG 20) to 2.5 mm
2
(AWG 13).
Installing the 4 to 20 mA current loop on the transmitter
For currents of 3 to 22 mA, a DC voltage between 16.5 V DC (3 mA),
or 8.0 V DC (22 mA) and 30 V DC must be present at the transmitter.
Fit 2-wire connecting cable in cable gland, cut to length and strip ends
(approx. 80 mm / 3.15").
Shorten the shield (if installed) to prevent short-circuiting:
Connect cable
1 Use a 4-pole terminal block (X8), Part No. 83 16 268, for the
Dräger Polytron 7000 – Observe the polarity of the connections.
Cut excess wires short or
2 secure them in centre terminals (Part No. 83 16 422).
1 Slide connecting terminal back into holder.
Secure cable in holder.
Fold up the installation notes and place them in the Dräger docking station for fu-
ture use during commissioning.
Refit raincover (protection against dust and splashing water).
Connecting to the central unit
Connect shield to earth of central unit (e.g. housing, earth bar, etc.).
Connecting the Dräger Polytron 7000 transmitter to a Dräger control unit
(such as Regard, QuadGard, Unigard or Polytron):
Further information about the connection can be found in the instructions for
the Dräger control unit.
Connecting the Dräger Polytron 7000 transmitter to control units with
a 4 to 20 mA interfaced made by other manufacturers:
For operation together with control units made by other manufacturers, care must
be taken that the voltage at the transmitter does not drop below 16.5 V at a current
of 3 mA and 8.0 V at a current of 22 mA. The supply voltage, the resistance of the
cable and the load and the resistance of any installed safety barrier must be taken
into account.
Further information about the connection can be found in the instructions for the
control unit being used.
00723758_1.eps
1
X8
2
+24 V
0 V
0 V
Signal

Table of Contents

Related product manuals